Provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations
Dual 10 ft. input cords with L6-30P plugs connect to separate primary and secondary single-phase power sources
Built-In L6-30R Outlet
Connects a single device or indirectly powers equipment through a 0U 208/240V PDU with L6-30P input (sold separately)
Automatic Transfer Switching
Dynamic solid-state (TRIAC) automatic transfer switching
Switches to secondary power source if primary source fails or becomes unstable
1–5 ms transfer time ensures uninterrupted operation of connected equipment
Built-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source
Multifunction Digital Display
Reports source A and source B input power status and other information, including power availability, line voltage, frequency, amps, kilowatts and power factor
Advanced Network Monitoring
LX Platform interface allows full remote access for power monitoring with email notifications via secure web browser, SNMP, telnet or SSH
Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities
Real-time load/current data with billing-grade accuracy (+/- 1 percent)
Automated alerts help prevent accidental overloads, power loss and downtime
Optional ENVIROSENSE module (sold separately) monitors temperature and humidity
10/100 Mbps auto-sensing allows optimal communication with 10/100 Base-T networks